Exciter Model: DC3A and ESDC3A
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Te < Mult*TimeStep then Te = Mult*TimeStep
- If 0.0 < Tr < 0.5*Mult*TimeStep then Tr = 0.0
ElseIf 0.5*Mult*TimeStep < Tr < Mult*TimeStep then Tr = Mult*TimeStep - If Vrmax < Vrmin then swap the values
- If Trh <= 0 then Trh = 0
- If Kv <= 0 then Kv = 0
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vr > Vrmax, then Vrmax = Vr or if Vr < Vrmin, then Vrmin = Vr
Model Equations and/or Block Diagrams
Parameters for DC3A:
| Tr | Filter time constant, sec. |
| Kv | Voltage error threshold min/max control action, p.u. (> 0.) |
| VrMax | Maximum control element output, p.u. |
| VrMin | Minimum control element output, p.u. |
| Trh | Rheostat full range travel time, sec. (> 0.) |
| Te | Exciter field time constant, sec. (> 0.) |
| Ke | Exciter field resistance line slope margin p.u. |
| Vemin | Exciter minimum limit |
| E1 | Field voltage value, 1 |
| SE1 | Saturation factor at E1 |
| E2 | Field voltage value, 2 |
| SE2 | Saturation factor at E2 |
Parameters for ESDC3A:
| Tr | Filter time constant, sec. |
| Trh | Rheostat full range travel time, sec. (> 0.) |
| Kv | Voltage error threshold min/max control action, p.u. (> 0.) |
| Vrmax | Maximum control element output, p.u. |
| Vrmin | Minimum control element output, p.u. |
| Te | Exciter field time constant, sec. (> 0.) |
| Ke | Exciter field resistance line slope margin p.u. |
| E1 | Field voltage value, 1 |
| SE1 | Saturation factor at E1 |
| E2 | Field voltage value, 2 |
| SE2 | Saturation factor at E2 |
| Spdmlt | If = 1, multiply output (Efd) by generator speed |
| exclim | If not 0, apply lower limit of 0. to exciter output |